Size selection, insulation, installation and brazing advice; the information you need on site, on one page.

Size chart

Copper tube outer diameters in inch and mm; insulated OD given separately for 9 mm and 13 mm PE.

SizeLiquid line ODGas line ODOD with 9 mm insulationOD with 13 mm insulationMin. bend radius
1/4" × 3/8"6.35 mm9.52 mm24.4 / 27.5 mm32.4 / 35.5 mm38 mm
1/4" × 1/2"6.35 mm12.70 mm24.4 / 30.7 mm32.4 / 38.7 mm51 mm
1/4" × 5/8"6.35 mm15.87 mm24.4 / 33.9 mm32.4 / 41.9 mm63 mm
3/8" × 5/8"9.52 mm15.87 mm27.5 / 33.9 mm35.5 / 41.9 mm63 mm
3/8" × 3/4"9.52 mm19.05 mm27.5 / 37.1 mm35.5 / 45.1 mm76 mm
1/2" × 3/4"12.70 mm19.05 mm30.7 / 37.1 mm38.7 / 45.1 mm76 mm

Why insulation matters

Prevents condensation

If the cold gas line touches ambient air, water droplets form on it; closed-cell PE prevents this and protects walls and ceilings.

Preserves efficiency

Heat gain along the run drops and the compressor works less; especially on long, sun-exposed runs this saves energy.

Withstands the outdoors

The UV-resistant white skin does not yellow or crack in the sun; extra protection with trunking or tape is still recommended outdoors.

Flame retardant

The insulation and PE skin are flame-retardant; they do not sustain a flame and add to fire safety in indoor installations.

Easy installation

Two pipes in one jacket: no separate insulation wrapping on site, shorter installation time.

Installation and brazing advice

Bending

  • Bend radius should be at least 4× the tube OD; tight bends narrow the cross-section.
  • Use a bending spring or mechanical bender on 1/2" and larger tube.
  • Do not pull the coil straight off the ground; roll the ring open, otherwise the tube twists.

Cutting and flaring

  • Use a tube cutter; a saw leaves swarf. Deburr the bore after cutting.
  • For R410A / R32 use a 45° flare and the torque values given by the unit manufacturer.

Brazing

  • Purge a low flow of nitrogen through the tube while brazing; it prevents oxide scale.
  • Slide the insulation back at least 10 cm from the joint; push it back after cooling.
  • Use phosphor–silver alloy rod for copper-to-copper joints; no flux needed.

Commissioning

  • Pressure test with nitrogen, then pull a vacuum of at least −0.1 MPa (below 750 microns).
  • Remove the end caps just before installation; do not leave open tube in a humid environment.

Frequently asked questions

Can you produce custom sizes or coil lengths?

Yes. We produce twin and single pipe from 1/4" to 3/4" with 9 or 13 mm insulation in coil lengths to your request. Send the size and quantity and we share a quote and lead time.

Do you produce under our own brand?

Yes. Your brand name and logo are printed on the white PE jacket; label and carton design are prepared to your request.

How is shipping handled?

Coils are shipped in cartons or on pallets with capped ends. Road, sea or air freight; export documents and certificate of origin are prepared by us.

Is the pipe suitable for R32?

Yes. Our tube is produced for high-pressure refrigerants such as R32 and R410A; follow the unit manufacturer’s torque values when flaring.

Tell us the diameter, we produce to your specification.

Wall thickness, insulation colour and pattern, coil length and brand printing are set to your order. Send your request and we will share a quote and lead time.